Back to the backflow review queue

Backflow assembly test: Station Dental

Approved

Filed Sep 3, 2024 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 3, 2024
Assembly type
RP
Serial number
W349599
Size
2
Test gauge serial
G-8945
Gauge calibration date
Apr 21, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-72-01196
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

178 Quarry Way
Owner: Lindqvist Holdings LLC
Parcel 067-72-01196