Backflow assembly test: Station Dental
ApprovedFiled Sep 20, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Sep 20, 2025
- Assembly type
- RP
- Serial number
- W349599
- Size
- 2
- Test gauge serial
- G-6211
- Gauge calibration date
- Apr 12, 2025
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.2 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-72-01196
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
178 Quarry Way
Owner: Lindqvist Holdings LLC
Parcel 067-72-01196