Backflow assembly test: 9074 Cedar Hollow Ln
Needs reviewFiled Nov 24, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Nov 24, 2026
- Assembly type
- DC
- Serial number
- Z973077
- Size
- 3/4
- Test gauge serial
- G-2555
- Gauge calibration date
- May 26, 2026
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-67-01019
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.