Back to the backflow review queue

Backflow assembly test: Maple Leaf Medical Offices

Approved

Filed Mar 15, 2025 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Mar 15, 2025
Assembly type
DC
Serial number
Z169764
Size
1
Test gauge serial
G-5525
Gauge calibration date
Jul 7, 2024
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Emerson Stroud, current on the service date
  • All required fields present
  • Address matches parcel 067-25-01074
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

9188 Orchard Trl
Owner: Pruitt Holdings LLC
Parcel 067-25-01074