Back to the backflow review queue

Backflow assembly test: 8327 Orchard Ct

Approved

Filed Jun 6, 2025 by Reese Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 6, 2025
Assembly type
DC
Serial number
A818350
Size
1
Test gauge serial
G-9076
Gauge calibration date
Sep 23, 2024
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Danner, current on the service date
  • All required fields present
  • Address matches parcel 067-54-01340
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

8327 Orchard Ct
Owner: Reese Wexler
Parcel 067-54-01340