Backflow assembly test: 9470 Pine Knoll Trl

Approved

Filed Aug 21, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 21, 2026
Assembly type
RP
Serial number
A649656
Size
1
Test gauge serial
G-9658
Gauge calibration date
Jul 3, 2026
Check valve 1
0.2 psid
Check valve 1 closed tight
No
Check valve 2
1.7 psid
Relief valve opened at
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-86-01280
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9470 Pine Knoll Trl
Owner: Rowan Lindqvist
Parcel 067-86-01280