Back to the backflow review queue

Backflow assembly test: Crossroads Diner

Approved

Filed Jun 6, 2025 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Jun 6, 2025
Assembly type
RP
Serial number
B637299
Size
1
Test gauge serial
G-1068
Gauge calibration date
Feb 14, 2025
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Avery Benton, current on the service date
  • All required fields present
  • Address matches parcel 067-44-01010
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7235 Meadow Lark Rd
Owner: Marsh Holdings LLC
Parcel 067-44-01010