Backflow assembly test: Crossroads Diner

Approved

Filed Jun 6, 2026 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jun 6, 2026
Assembly type
RP
Serial number
B637299
Size
1
Test gauge serial
G-7400
Gauge calibration date
Apr 18, 2026
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-44-01010
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.