Backflow assembly test: 4667 Quarry Way
ApprovedFiled Jul 7, 2025 by Emerson Stroud, Keystone Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 7, 2025
- Assembly type
- RP
- Serial number
- K809722
- Size
- 3/4
- Test gauge serial
- G-7180
- Gauge calibration date
- Feb 3, 2025
- Check valve 1
- 3.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-55-01088
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.