Backflow assembly test: 8725 Mill Creek Dr
ApprovedFiled Jul 4, 2026 by Avery Benton, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 4, 2026
- Assembly type
- RP
- Serial number
- W365372
- Size
- 3/4
- Test gauge serial
- G-4030
- Gauge calibration date
- Dec 29, 2025
- Check valve 1
- 4.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 4.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Benton, current on the service date
- All required fields present
- Address matches parcel 067-58-01358
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8725 Mill Creek Dr
Owner: Jamie Whitcomb
Parcel 067-58-01358