Back to the backflow review queue
Backflow assembly test: 3919 Spring Branch Ln
ApprovedFiled Apr 10, 2026 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 10, 2026
- Assembly type
- DC
- Serial number
- B323872
- Size
- 3/4
- Test gauge serial
- G-8530
- Gauge calibration date
- Nov 17, 2025
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-92-01094
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.
Property
3919 Spring Branch Ln
Owner: Taylor Pruitt
Parcel 067-92-01094