Backflow assembly test: 1854 Laurel Trl

Approved

Filed Sep 9, 2023 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 9, 2023
Assembly type
RP
Serial number
K204758
Size
1
Test gauge serial
G-4329
Gauge calibration date
Jun 22, 2023
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-43-01027
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

1854 Laurel Trl
Owner: Emerson Whitcomb
Parcel 067-43-01027