Backflow assembly test: 4226 Stone Gate Ln
ApprovedFiled Sep 12, 2023 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Sep 12, 2023
- Assembly type
- RP
- Serial number
- A723330
- Size
- 3/4
- Test gauge serial
- G-8804
- Gauge calibration date
- Apr 5, 2023
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-65-01348
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.