Back to the backflow review queue

Backflow assembly test: 4226 Stone Gate Ln

Approved

Filed Oct 19, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 19, 2024
Assembly type
RP
Serial number
A723330
Size
3/4
Test gauge serial
G-1239
Gauge calibration date
Jun 26, 2024
Check valve 1
7.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-65-01348
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4226 Stone Gate Ln
Owner: Hayden Benton
Parcel 067-65-01348