Back to the backflow review queue

Backflow assembly test: 1558 Cedar Hollow Trl

Approved

Filed Oct 8, 2025 by Quinn Wexler, Lakeside Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Oct 8, 2025
Assembly type
PVB
Serial number
W427360
Size
1
Test gauge serial
G-6694
Gauge calibration date
Dec 17, 2024
Check valve 1
6.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Wexler, current on the service date
  • All required fields present
  • Address matches parcel 067-62-01301
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1558 Cedar Hollow Trl
Owner: Emerson Danner
Parcel 067-62-01301