Backflow assembly test: Blue Heron Grill
ApprovedFiled Apr 6, 2024 by Quinn Wexler, Lakeside Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Apr 6, 2024
- Assembly type
- DC
- Serial number
- B900469
- Size
- 1 1/2
- Test gauge serial
- G-9455
- Gauge calibration date
- Dec 30, 2023
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Wexler, current on the service date
- All required fields present
- Address matches parcel 067-54-01310
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1797 Stone Gate Dr
Owner: Harlow Holdings LLC
Parcel 067-54-01310