Backflow assembly test: 4739 Mill Creek Ct
ApprovedFiled Aug 8, 2023 by Emerson Stroud, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Aug 8, 2023
- Assembly type
- PVB
- Serial number
- A313902
- Size
- 1
- Test gauge serial
- G-4271
- Gauge calibration date
- Feb 24, 2023
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Emerson Stroud, current on the service date
- All required fields present
- Address matches parcel 067-15-01121
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.