Backflow assembly test: 4217 Spring Branch Trl
ApprovedFiled Dec 22, 2024 by Quinn Okafor, Heritage Plumbing & Backflow. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Dec 22, 2024
- Assembly type
- RP
- Serial number
- A710193
- Size
- 1
- Test gauge serial
- G-4940
- Gauge calibration date
- May 18, 2024
- Check valve 1
- 3.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Quinn Okafor, current on the service date
- All required fields present
- Address matches parcel 071-60-01240
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.