Backflow assembly test: 9051 Sycamore Trl
ApprovedFiled Jul 2, 2026 by Avery Whitcomb, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 2, 2026
- Assembly type
- RP
- Serial number
- B752524
- Size
- 1
- Test gauge serial
- G-9799
- Gauge calibration date
- Apr 18, 2025
- Check valve 1
- 0 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Whitcomb, current on the service date
- All required fields present
- Address matches parcel 071-89-01242
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.