Backflow assembly test: 8746 Turkey Hill Dr

Approved

Filed Aug 10, 2025 by Drew Hollins, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Aug 10, 2025
Assembly type
PVB
Serial number
W902935
Size
3/4
Test gauge serial
G-6791
Gauge calibration date
Nov 3, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Hollins, current on the service date
  • All required fields present
  • Address matches parcel 071-73-01077
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.