Backflow assembly test: 6509 Quarry Dr

Approved

Filed Nov 8, 2025 by Drew Hollins, Summit Backflow Testing. Filed from a phone.

Report

Date of service
Nov 8, 2025
Assembly type
RP
Serial number
K867448
Size
1
Test gauge serial
G-3672
Gauge calibration date
Nov 25, 2024
Check valve 1
0.5 psid
Check valve 1 closed tight
No
Check valve 2
3.7 psid
Relief valve opened at
3.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Drew Hollins, current on the service date
  • All required fields present
  • Address matches parcel 071-71-01037
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

6509 Quarry Dr
Owner: Shawn Danner
Parcel 071-71-01037