Backflow assembly test: 4417 Hickory Dr

Approved

Filed Oct 15, 2025 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 15, 2025
Assembly type
RP
Serial number
Z435394
Size
1
Test gauge serial
G-3466
Gauge calibration date
Feb 2, 2025
Check valve 1
0.3 psid
Check valve 1 closed tight
No
Check valve 2
2 psid
Relief valve opened at
2.2 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Vance, current on the service date
  • All required fields present
  • Address matches parcel 071-96-01203
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4417 Hickory Dr
Owner: Alex Pruitt
Parcel 071-96-01203