Backflow assembly test: 1717 Fox Run Dr

Approved

Filed May 28, 2024 by Quinn Okafor, Heritage Plumbing & Backflow. Filed from a phone.

Report

Date of service
May 28, 2024
Assembly type
RP
Serial number
B234851
Size
1
Test gauge serial
G-7339
Gauge calibration date
Sep 9, 2023
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Quinn Okafor, current on the service date
  • All required fields present
  • Address matches parcel 071-82-01050
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.