Backflow assembly test: Blue Heron Animal Hospital

Approved

Filed Oct 13, 2024 by Sam Nguyen, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 13, 2024
Assembly type
DC
Serial number
W223767
Size
2
Test gauge serial
G-8138
Gauge calibration date
Jul 14, 2024
Check valve 1
4.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Nguyen, current on the service date
  • All required fields present
  • Address matches parcel 071-49-01246
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3830 Mill Creek Rd
Owner: Harlow Holdings LLC
Parcel 071-49-01246