Backflow assembly test: 6610 Stone Gate Ln
ApprovedFiled Oct 18, 2025 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 18, 2025
- Assembly type
- DC
- Serial number
- Z398779
- Size
- 3/4
- Test gauge serial
- G-9588
- Gauge calibration date
- Feb 18, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 071-18-01026
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6610 Stone Gate Ln
Owner: Jordan Hollins
Parcel 071-18-01026