Back to the backflow review queue
Backflow assembly test: Blue Heron Apartments
ApprovedFiled Sep 2, 2026 by Blake Danner, Summit Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 2, 2026
- Assembly type
- DC
- Serial number
- Z957074
- Size
- 4
- Test gauge serial
- G-3369
- Gauge calibration date
- Aug 24, 2025
- Check valve 1
- 0.9 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Blake Danner, current on the service date
- All required fields present
- Address matches parcel 071-13-01033
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3255 Fox Run Dr
Owner: Ellery Holdings LLC
Parcel 071-13-01033