Backflow assembly test: 7016 Sycamore Trl
ApprovedFiled Oct 23, 2025 by Sam Nguyen, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Oct 23, 2025
- Assembly type
- DC
- Serial number
- K231294
- Size
- 3/4
- Test gauge serial
- G-5168
- Gauge calibration date
- Sep 1, 2025
- Check valve 1
- 8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Nguyen, current on the service date
- All required fields present
- Address matches parcel 071-96-01016
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7016 Sycamore Trl
Owner: Alex Nguyen
Parcel 071-96-01016