Back to the backflow review queue
Backflow assembly test: Riverside Taqueria
ApprovedFiled Jan 24, 2025 by Avery Whitcomb, Keystone Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jan 24, 2025
- Assembly type
- DC
- Serial number
- K366299
- Size
- 2
- Test gauge serial
- G-4667
- Gauge calibration date
- Dec 4, 2024
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Avery Whitcomb, current on the service date
- All required fields present
- Address matches parcel 071-80-01241
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
8460 Quarry Way
Owner: Fairley Holdings LLC
Parcel 071-80-01241