Backflow assembly test: 5732 Orchard Way
ApprovedFiled Jul 21, 2026 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jul 21, 2026
- Assembly type
- DC
- Serial number
- A965670
- Size
- 1
- Test gauge serial
- G-2194
- Gauge calibration date
- May 29, 2026
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 071-82-01172
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.