Back to the backflow review queue

Backflow assembly test: 3505 Meadow Lark Ln

Approved

Filed Aug 23, 2026 by Hayden Danner, Keystone Plumbing & Backflow. Filed from a phone.

Report

Date of service
Aug 23, 2026
Assembly type
PVB
Serial number
K884809
Size
3/4
Test gauge serial
G-3181
Gauge calibration date
Jul 4, 2026
Check valve 1
6.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Hayden Danner, current on the service date
  • All required fields present
  • Address matches parcel 071-95-01102
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

3505 Meadow Lark Ln
Owner: Quinn Calloway
Parcel 071-95-01102