Back to the backflow review queue
Backflow assembly test: Corner Diner
ApprovedFiled Jun 2, 2026 by Jordan Vance, Heritage Plumbing & Backflow. Filed from a phone.
Report
- Date of service
- Jun 2, 2026
- Assembly type
- RP
- Serial number
- K715436
- Size
- 1 1/2
- Test gauge serial
- G-8066
- Gauge calibration date
- Aug 20, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Jordan Vance, current on the service date
- All required fields present
- Address matches parcel 071-94-01066
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1392 Cedar Hollow Rd
Owner: Hollins Holdings LLC
Parcel 071-94-01066