Backflow assembly test: 929 Sycamore Ln

Approved

Filed Dec 15, 2025 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.

Report

Date of service
Dec 15, 2025
Assembly type
RP
Serial number
Z489997
Size
3/4
Test gauge serial
G-6128
Gauge calibration date
Apr 11, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-82-01287
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

929 Sycamore Ln
Owner: Avery Ashby
Parcel 073-82-01287