Back to the backflow review queue

Backflow assembly test: 2624 Spring Branch Dr

Approved

Filed Feb 27, 2025 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Feb 27, 2025
Assembly type
PVB
Serial number
Z141658
Size
3/4
Test gauge serial
G-8283
Gauge calibration date
Sep 6, 2024
Check valve 1
3.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-71-01122
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

2624 Spring Branch Dr
Owner: Riley Ashby
Parcel 073-71-01122