Back to the backflow review queue

Backflow assembly test: 4265 Sycamore Rd

Approved

Filed Jul 20, 2025 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Jul 20, 2025
Assembly type
RP
Serial number
A452459
Size
3/4
Test gauge serial
G-8994
Gauge calibration date
Jan 3, 2025
Check valve 1
8.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-81-01209
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

4265 Sycamore Rd
Owner: Blake Okafor
Parcel 073-81-01209