Backflow assembly test: 1880 Orchard Way

Approved

Filed May 18, 2025 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
May 18, 2025
Assembly type
RP
Serial number
B159910
Size
1
Test gauge serial
G-8503
Gauge calibration date
Apr 12, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
3.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-28-01343
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1880 Orchard Way
Owner: Morgan Whitcomb
Parcel 073-28-01343