Backflow assembly test: 5293 Meadow Lark Rd
ApprovedFiled Sep 29, 2025 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Sep 29, 2025
- Assembly type
- PVB
- Serial number
- K774858
- Size
- 3/4
- Test gauge serial
- G-4756
- Gauge calibration date
- Dec 27, 2024
- Check valve 1
- 6.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-20-01136
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5293 Meadow Lark Rd
Owner: Parker Marsh
Parcel 073-20-01136