Backflow assembly test: 4408 Turkey Hill Dr

Approved

Filed Jul 8, 2023 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.

Report

Date of service
Jul 8, 2023
Assembly type
DC
Serial number
Z931457
Size
1
Test gauge serial
G-1886
Gauge calibration date
Nov 29, 2022
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Kessler, current on the service date
  • All required fields present
  • Address matches parcel 073-96-01048
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4408 Turkey Hill Dr
Owner: Drew Brandt
Parcel 073-96-01048