Backflow assembly test: 9710 Cedar Hollow Rd

Approved

Filed Aug 8, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Aug 8, 2026
Assembly type
RP
Serial number
K959082
Size
1
Test gauge serial
G-4329
Gauge calibration date
Nov 2, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-99-01233
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

9710 Cedar Hollow Rd
Owner: Taylor Brandt
Parcel 073-99-01233