Backflow assembly test: Main Street Market

Approved

Filed May 15, 2025 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
May 15, 2025
Assembly type
RP
Serial number
B384982
Size
1
Test gauge serial
G-8159
Gauge calibration date
Jan 13, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-56-01022
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2371 Sycamore Trl
Owner: Vance Holdings LLC
Parcel 073-56-01022