Backflow assembly test: Blue Heron Taqueria
ApprovedFiled Mar 28, 2025 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Mar 28, 2025
- Assembly type
- DC
- Serial number
- Z685560
- Size
- 1 1/2
- Test gauge serial
- G-7000
- Gauge calibration date
- Jun 14, 2024
- Check valve 1
- 4.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Vance, current on the service date
- All required fields present
- Address matches parcel 073-74-01104
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.