Back to the backflow review queue
Backflow assembly test: Crossroads Taqueria
ApprovedFiled Jul 30, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jul 30, 2026
- Assembly type
- DC
- Serial number
- Z423042
- Size
- 2
- Test gauge serial
- G-8523
- Gauge calibration date
- Mar 2, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Fairley, current on the service date
- All required fields present
- Address matches parcel 073-70-01208
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3053 Mill Creek Way
Owner: Whitcomb Holdings LLC
Parcel 073-70-01208