Back to the backflow review queue

Backflow assembly test: Hilltop Self Storage

Approved

Filed Jul 22, 2026 by Parker Fairley, Heritage Backflow Testing. Filed from a phone.

Report

Date of service
Jul 22, 2026
Assembly type
RP
Serial number
Z906271
Size
1
Test gauge serial
G-7353
Gauge calibration date
May 14, 2026
Check valve 1
6.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.4 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Parker Fairley, current on the service date
  • All required fields present
  • Address matches parcel 073-20-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5928 Laurel Way
Owner: Nguyen Holdings LLC
Parcel 073-20-01241