Backflow assembly test: Maple Leaf Brewing Co
ApprovedFiled Jul 11, 2026 by Logan Vance, Ridge Backflow Testing. Read in from a paper form and confirmed by staff.
Report
- Date of service
- Jul 11, 2026
- Assembly type
- RP
- Serial number
- B454893
- Size
- 4
- Test gauge serial
- G-9911
- Gauge calibration date
- Oct 14, 2025
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Logan Vance, current on the service date
- All required fields present
- Address matches parcel 073-11-01093
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
5362 Meadow Lark Ln
Owner: Marsh Holdings LLC
Parcel 073-11-01093