Back to the backflow review queue

Backflow assembly test: Crossroads Grill

Approved

Filed Mar 7, 2024 by Logan Vance, Ridge Backflow Testing. Filed from a phone.

Report

Date of service
Mar 7, 2024
Assembly type
RP
Serial number
K999092
Size
1
Test gauge serial
G-9299
Gauge calibration date
Oct 21, 2023
Check valve 1
8.7 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
2.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Logan Vance, current on the service date
  • All required fields present
  • Address matches parcel 073-94-01045
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

2627 Meadow Lark Way
Owner: Pruitt Holdings LLC
Parcel 073-94-01045