Backflow assembly test: Blue Heron Diner
ApprovedFiled Oct 26, 2025 by Rowan Kessler, Valley Backflow Testing. Filed from a phone.
Report
- Date of service
- Oct 26, 2025
- Assembly type
- RP
- Serial number
- Z525602
- Size
- 4
- Test gauge serial
- G-3360
- Gauge calibration date
- Mar 3, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Relief valve opened at
- 1.4 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Kessler, current on the service date
- All required fields present
- Address matches parcel 073-84-01213
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.