Back to the backflow review queue

Backflow assembly test: 4258 Sycamore Ln

Approved

Filed Nov 21, 2024 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Nov 21, 2024
Assembly type
RP
Serial number
A983488
Size
1
Test gauge serial
G-4642
Gauge calibration date
Jul 19, 2024
Check valve 1
4.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.5 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-57-01100
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4258 Sycamore Ln
Owner: Sam Benton
Parcel 075-57-01100