Backflow assembly test: Riverside Grill

Approved

Filed Oct 10, 2025 by Jordan Wexler, Summit Plumbing & Backflow. Filed from a phone.

Report

Date of service
Oct 10, 2025
Assembly type
DC
Serial number
A188660
Size
1 1/2
Test gauge serial
G-3369
Gauge calibration date
Jun 6, 2025
Check valve 1
6 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-99-01053
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5517 Pine Knoll Ct
Owner: Ellery Holdings LLC
Parcel 075-99-01053