Backflow assembly test: Riverside Grill

Approved

Filed Sep 30, 2026 by Blake Pruitt, Patriot Plumbing & Backflow. Filed from a phone.

Report

Date of service
Sep 30, 2026
Assembly type
DC
Serial number
A188660
Size
1 1/2
Test gauge serial
G-8570
Gauge calibration date
Feb 20, 2026
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.3 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Blake Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 075-99-01053
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved automatically, because nothing was flagged. The property's next due date is set and the owner gets a receipt.

Property

5517 Pine Knoll Ct
Owner: Ellery Holdings LLC
Parcel 075-99-01053