Back to the backflow review queue

Backflow assembly test: 780 Pine Knoll Trl

Approved

Filed Jan 19, 2025 by Jordan Wexler, Summit Plumbing & Backflow. Read in from a paper form and confirmed by staff.

Report

Date of service
Jan 19, 2025
Assembly type
RP
Serial number
K332010
Size
1
Test gauge serial
G-8377
Gauge calibration date
Jul 26, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.4 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Jordan Wexler, current on the service date
  • All required fields present
  • Address matches parcel 075-97-01256
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

780 Pine Knoll Trl
Owner: Jordan Hollins
Parcel 075-97-01256