Back to the backflow review queue
Backflow assembly test: 780 Pine Knoll Trl
ApprovedFiled Jan 2, 2026 by Alex Wexler, Heritage Backflow Testing. Filed from a phone.
Report
- Date of service
- Jan 2, 2026
- Assembly type
- RP
- Serial number
- K332010
- Size
- 1
- Test gauge serial
- G-8681
- Gauge calibration date
- Aug 14, 2025
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Alex Wexler, current on the service date
- All required fields present
- Address matches parcel 075-97-01256
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
780 Pine Knoll Trl
Owner: Jordan Hollins
Parcel 075-97-01256